OI-6000 CSA #152 Sensor Assembly for Combustible Gas

The Otis Instruments OI-6000 Series Ambient Air Combustible Gas Detector is a versatile assembly that uses an infrared sensor element to detect combustible gases in ambient air. The assembly is certified to CSA 22.2 No. 152 and ANSI/ISA 12.13.01-2013 Performance standards for quick response to combustible gas. Wired power (12 to 35 VDC) with 4-20 mA analog and RS-485 Modbus outputs standard. Magnetic switches allow for nonintrusive calibration while in the field as well as full system settings and diagnostics while remaining Class I Division 1 Groups C & D Certified.
Part Number Formula OI-6000-IR-152-X-X-O — No relays installed OI-6000-IR-152-X-R-O — 2 Dry contact relays installed
Sensor Type: Infrared Sensor Element
Operating Voltage: Wired Power (3-Wire) 12 to 35 VDC
Current Draw: 1 Amp Maximum
Protection:
• Power Electromagnetic Interference (EMI) Filter
• 4-20 mA Surge Suppression
• RS-485 Surge Suppression
Display Screen:
• 102×64 Resolution Graphical LCD Screen
• Transflective (Sunlight Readable) with white LED Backlight
Interface:
• 3 Push-Buttons (MENU, ADD, and SUB)
• 3 Magnetic Non-Intrusive Switches for Calibration (MENU, ADD and SUB)
Customizable Settings: 2 Individually-Configurable Alarm LED/Relay Set-Points
Tamb Temperature Range: -40°C to +54°C / -40°F to 130°F
Wired Analog Output:
• 4-20 mA (3-Wire)
• Fault Terminal
• Optional 2 Dry-Contact Relays with Replaceable 4 Amp Fuses
Digital Output: RS-485 Modbus
Remote Mount Control Unit (Optional Additional Feature): OI-6800 Remote Control Unit
• Allows full operational control of the remotely connected OI-6000-IR-152-X-X-O
• Available in Explosion Proof and Non-Explosion Proof Enclosure Option
• Ability to include an additional 2 Dry-Contact Relays
• Ability to add a GEN II 900 MHz or 2.4 GHz Radio for Wirefree Signal Reporting to other Otis Monitors
Product Dimensions: 5.5″ T x 6″ W x 7″ H (8” W x 17” H Maximum w/ Attachments)
Total Weight: 5.75 lbs.
Hazardous Location Certifications and Approvals:
• Class I, Division 1, Groups C and D T4
• Ex d ib IIB T4 Gb
• Class I, Zone 0, IIB Aex d ib T4 Gb
• CSA 22.2 No. 152
• ANSI/ISA 12.13.01-2013
• Tamb –40°C to +54°C
Hardware Warranty: Limited one year
Sensor Element Warranty: 24 Months, subject to Otis verification of element condition
Relays: None, Two Dry Contact Relays
OI-6000-IR-152-CB-KIT | OI-6000 Control Board with LCD Screen Installed |